Rockwell Automation FactoryTalk Services Platform
Overview
Rockwell Automation has disclosed a significant vulnerability in its FactoryTalk Services Platform (FTSP) version 6.60, which could allow attackers to impersonate authorized users. This flaw arises from weak authentication practices, specifically the inability of the application to properly validate JSON Web Tokens (JWT). As a result, low-privilege users could exploit this vulnerability to gain unauthorized access to critical system configurations and permissions. Organizations using FTSP are urged to apply a specific patch (RAID 1158263) or the February 2026 Patch Roll-up to mitigate this risk. As of now, there have been no reports of active exploitation in the wild, but users are advised to follow best security practices to protect their systems.
Key Takeaways
- Affected Systems: Rockwell Automation FactoryTalk Services Platform (FTSP) version 6.60
- Action Required: Users should apply patch RAID 1158263 or the February 2026 Patch Roll-up.
- Timeline: Disclosed on July 21, 2026
Original Article Summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to impersonate an authorized user on the FTSP server, resulting in unauthorized access to system configurations. The following versions of Rockwell Automation FactoryTalk Services Platform are affected: FactoryTalk Directory (FTSP) 6.60 CVSS Vendor Equipment Vulnerabilities v3 7.8 Rockwell Automation Rockwell Automation FactoryTalk Services Platform Weak Authentication Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2026-10714 A security issue exists within FactoryTalk Services Platform (FTSP), allowing an attacker to bypass JWT signature validation during Okta Web Authentication. The vulnerability stems from the application not verifying that the JWT algorithm is configured for RSA, enabling an attacker to set the algorithm to "none" and craft forged tokens. This could allow an authenticated low-privilege user to impersonate any authorized user on the FTSP server, resulting in unauthorized access to system configuration and the ability to grant permissions to other systems protected by FTSP. View CVE Details Affected Products Rockwell Automation FactoryTalk Services Platform Vendor: Rockwell Automation Product Version: Rockwell Automation FactoryTalk Directory (FTSP): 6.60 Product Status: known_affected Remediations Mitigation Users using FactoryTalk Services Platform v6.60 should apply either the individual patch (RAID 1158263) or the February 2026 Patch Roll-up, or later update. Mitigation Users using the affected software, who are not able to upgrade to one of the corrected versions, should use Rockwell's security best practices. https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight Mitigation For more information, refer to Rockwell Automation's security advisory SD1786 page. https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1786.html Relevant CWE: CWE-1390 Weak Authentication Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.8 HIGH CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H 4.0 8.8 HIGH CVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H Acknowledgments Rockwell Automation reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely. Revision History Initial Release Date: 2026-07-21 Date Revision Summary 2026-07-21 1 Initial Republication of Rockwell Automation SD1786 Legal Notice and Terms of Use
Impact
Rockwell Automation FactoryTalk Services Platform (FTSP) version 6.60
Exploitation Status
No active exploitation has been reported at this time. However, organizations should still apply patches promptly as proof-of-concept code may exist.
Timeline
Disclosed on July 21, 2026
Remediation
Users should apply patch RAID 1158263 or the February 2026 Patch Roll-up. For those unable to upgrade, Rockwell recommends following their security best practices.
Additional Information
This threat intelligence is aggregated from trusted cybersecurity sources. For the most up-to-date information, technical details, and official vendor guidance, please refer to the original article linked below.