Haiwell IoT Cloud HMI Gateway
Overview
A serious security vulnerability has been discovered in the Haiwell IoT Cloud HMI Gateway, specifically in version 3.40.1.12. This flaw allows attackers to inject and execute arbitrary operating system commands with root privileges, posing a significant risk to critical infrastructure sectors like energy and water management. The vulnerability stems from improper input handling in the Net Check feature, which fails to sanitize user inputs effectively. Although no active exploitation has been reported yet, organizations using this product should take immediate action to mitigate potential risks. Haiwell has released a patch (version Scada-v3.50.1.19) to address this issue, which users are urged to implement as soon as possible.
Key Takeaways
- Affected Systems: Haiwell IoT Cloud HMI Gateway version 3.40.1.12
- Action Required: Haiwell has released a patch to resolve the vulnerability, specifically patch version Scada-v3.
- Timeline: Disclosed on 2026-08-13
Original Article Summary
View CSAF Summary Successful exploitation of this vulnerability may allow an attacker to inject and execute arbitrary OS commands with root privileges. The following versions of Haiwell IoT Cloud HMI Gateway are affected: Haiwell IoT Cloud HMI Gateway 3.40.1.12 (CVE-2026-19188) CVSS Vendor Equipment Vulnerabilities v3 10 Haiwell Haiwell IoT Cloud HMI Gateway Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Background Critical Infrastructure Sectors: Energy, Critical Manufacturing, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: China Vulnerabilities Expand All + CVE-2026-19188 A critical OS command injection vulnerability has been identified in the Haiwell IoT Cloud HMI Gateway product. The vulnerability exists in the Net Check feature accessible via the /setting endpoint. The cmdPing Socket.io event fails to properly sanitize user-supplied input before passing it to the underlying operating system, allowing an attacker to inject and execute arbitrary OS commands with root privileges View CVE Details Affected Products Haiwell IoT Cloud HMI Gateway Vendor: Haiwell Product Version: Haiwell Haiwell IoT Cloud HMI Gateway: 3.40.1.12 Product Status: known_affected Remediations Mitigation Haiwell has addressed the issue in patch version number Scada-v3.50.1.19, which is available for download on their website: https://en.haiwell.com/app/system/entrance.php?m=include&c=access&a=dodown&lang=en&id=361 https://en.haiwell.com/app/system/entrance.php?m=include&c=access&a=dodown&lang=en&id=361 Relevant CWE: CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 10 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H 4.0 10 CRITICAL CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H Acknowledgments Fiqram Akmal reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-08-13 Date Revision Summary 2026-08-13 1 Initial Publication Legal Notice and Terms of Use
Impact
Haiwell IoT Cloud HMI Gateway version 3.40.1.12
Exploitation Status
No active exploitation has been reported at this time. However, organizations should still apply patches promptly as proof-of-concept code may exist.
Timeline
Disclosed on 2026-08-13
Remediation
Haiwell has released a patch to resolve the vulnerability, specifically patch version Scada-v3.50.1.19, which is available for download on their website.
Additional Information
This threat intelligence is aggregated from trusted cybersecurity sources. For the most up-to-date information, technical details, and official vendor guidance, please refer to the original article linked below.