AVEVA Enterprise SCADA
Overview
A vulnerability has been identified in AVEVA Enterprise SCADA that could allow attackers to manipulate serialized data, potentially leading to code execution during deserialization. This issue affects multiple versions of the software, including Enterprise SCADA 2025 and earlier versions back to 2022. Users are advised to switch from 'Binary Formatter' to 'Json' serialization and to change the 'AcceptBinaryFormattedData' setting to 'false'. Additionally, AVEVA recommends auditing device permissions and ensuring that only trusted users have operator rights. While there are no reports of active exploitation of this vulnerability, organizations are urged to take defensive measures to protect their systems. For detailed remediation steps, users should refer to the relevant knowledge base articles provided by AVEVA.
Key Takeaways
- Affected Systems: AVEVA Enterprise SCADA 2025, Enterprise SCADA 2024, Enterprise SCADA 2023, Enterprise SCADA 2022
- Action Required: Change 'Mode' setting from 'Binary Formatter' to 'Json'; change 'AcceptBinaryFormattedData' setting from 'true' to 'false'; re-cache the XOS Event Handlers assembly; configure clients to only use JSON serialization; migrate HMI displays; audit devices and permissions; disallow BLT Test clients in production environments.
- Timeline: Disclosed on 2026-08-13
Original Article Summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to tamper with serialized data, potentially resulting in code execution during deserialization. The following versions of AVEVA Enterprise SCADA are affected: Enterprise SCADA 2025 (CVE-2025-7639) Enterprise SCADA >=2024|=2023|=2022|=2024|=2023|=2022| "Mode" setting from 'Binary Formatter' to 'Json'. Change "BinarySerializer" -> "AcceptBinaryFormattedData" setting from 'true' to 'false'. Re-cache the XOS Event Handlers assembly Mitigation Client Components: Configure clients/products that interface with Enterprise SCADA to only use JSON serialization. Mitigation HMI: Migrate HMI displays Mitigation For step-by-step instructions on where and how to apply these configuration settings, how to migrate HMI displays, compatible server-client versions list, and additional details please refer to KB117814 "AVEVA Midstream Product Bulletin - Removal of Binary Formatter" https://softwaresupportsp.aveva.com/en-US/knowledge/details/000117814?lang=en_US Mitigation AVEVA recommends the following general defensive measures: Audit devices, network topology, and perimeter defences to ensure all applicable security best practices from AVEVA's Enterprise SCADA Reference System Architecture are adhered to. Audit assigned permissions to ensure that only trusted users are given "DNA Authority - Operator" rights: https://docs.aveva.com/bundle/scada-ent-2025/page/651008.html Disallow BLT Test clients in production environmentsFor additional details on defensive measures, refer to Section 5 of KB117814 "AVEVA Midstream Product Bulletin - Removal of Binary Formatter https://docs.aveva.com/bundle/scada-ent-2025/page/651008.html Mitigation For more information on this vulnerability, including security updates, users should see the security bulletin AVEVA-2026-005. https://www.aveva.com/content/dam/aveva/documents/support/cyber-security-updates/SecurityBulletin_AVEVA-2026-005.pdf Relevant CWE: CWE-502 Deserialization of Untrusted Data Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.1 HIGH CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:L/I:H/A:H 4.0 6.1 MEDIUM CVSS:4.0/AV:N/AC:H/AT:N/PR:L/UI:N/VC:L/VI:H/VA:H/SC:N/SI:N/SA:N Acknowledgments AVEVA reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks. Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity. Revision History Initial Release Date: 2026-08-13 Date Revision Summary 2026-08-13 1 Initial Republication of AVEVA security bulletin AVEVA-2026-005 Legal Notice and Terms of Use
Impact
AVEVA Enterprise SCADA 2025, Enterprise SCADA 2024, Enterprise SCADA 2023, Enterprise SCADA 2022
Exploitation Status
No active exploitation has been reported at this time. However, organizations should still apply patches promptly as proof-of-concept code may exist.
Timeline
Disclosed on 2026-08-13
Remediation
Change 'Mode' setting from 'Binary Formatter' to 'Json'; change 'AcceptBinaryFormattedData' setting from 'true' to 'false'; re-cache the XOS Event Handlers assembly; configure clients to only use JSON serialization; migrate HMI displays; audit devices and permissions; disallow BLT Test clients in production environments.
Additional Information
This threat intelligence is aggregated from trusted cybersecurity sources. For the most up-to-date information, technical details, and official vendor guidance, please refer to the original article linked below.
Related Topics: This incident relates to Phishing, CVE, Vulnerability.