Johnson Controls EasyIO Neo Series EC and CW Controllers
Overview
Johnson Controls has reported a vulnerability in its EasyIO Neo Series EC and CW Controllers that could allow attackers to intercept sensitive information, such as credentials and session data, transmitted in cleartext over the network. The affected versions include EC Controllers V3.3b62 and V3.3b63, and CW Controllers V3.3b24 and V3.3b25. This issue is significant because it impacts critical infrastructure sectors like manufacturing, government services, and energy systems, where secure data transmission is essential. Users are urged to upgrade to fixed firmware versions, which include improvements like disabling HTTP communication by default. Until updates can be applied, Johnson Controls recommends several mitigations, such as enforcing HTTPS/TLS and isolating devices on a secured network.
Key Takeaways
- Affected Systems: Johnson Controls EasyIO Neo Series EC Controllers V3.3b62, V3.3b63; EasyIO Neo Series CW Controllers V3.3b24, V3.3b25
- Action Required: Users should upgrade to EC firmware V3.
- Timeline: Disclosed on 2026-10-01
Original Article Summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker tointercept and read sensitive information, including credentials andsession data. The following versions of Johnson Controls EasyIO Neo Series EC and CW Controllers are affected: EasyIO Neo Series EC Controllers V3.3b62 (CVE-2026-64893) EasyIO Neo Series EC Controllers V3.3b63 (CVE-2026-64893) EasyIO Neo Series CW Controllers V3.3b24 (CVE-2026-64893) EasyIO Neo Series CW Controllers V3.3b25 (CVE-2026-64893) CVSS Vendor Equipment Vulnerabilities v3 5.4 Johnson Controls Johnson Controls EasyIO Neo Series EC and CW Controllers Cleartext Transmission of Sensitive Information Background Critical Infrastructure Sectors: Critical Manufacturing, Commercial Facilities, Government Services and Facilities, Transportation Systems, Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Ireland Vulnerabilities Expand All + CVE-2026-64893 Johnson Controls is aware of a vulnerability in EasyIO Neo which may allow an attacker to intercept and read sensitive information, including credentials and session data, transmitted in cleartext over the network. Successful exploitation could result in technical or operational impact. EasyIO Neo is a programmable building automation edge controller used to manage and automate HVAC, lighting, and energy systems in commercial buildings through a web-based interface. View CVE Details Affected Products Johnson Controls EasyIO Neo Series EC and CW Controllers Vendor: Johnson Controls Product Version: Johnson Controls EasyIO Neo Series EC Controllers: V3.3b62, Johnson Controls EasyIO Neo Series EC Controllers: V3.3b63, Johnson Controls EasyIO Neo Series CW Controllers: V3.3b24, Johnson Controls EasyIO Neo Series CW Controllers: V3.3b25 Product Status: known_affected Remediations Mitigation Johnson Controls released fixed versions for EasyIO Neo Series EC and CW Controllers. Users should upgrade to the fixed version or later as soon as operationally feasible. HTTP communication has been disabled by default in the latest version. The fix is available in EC firmware V3.3b64 andCW firmware V3.3b26. Contact your Johnson Controls representative or visitthe Johnson Controls Trust Center. Mitigation Before applying updates in production ICS/OT environments, users should review operational impact, backup relevant configurations, test updates in a non-production environment where feasible, and follow applicable change-management and safety procedures. Mitigation If immediate update is not possible, Johnson Controls recommends the following mitigations: Enable and enforce HTTPS/TLS for all web-based management access to the device. Disable HTTP access entirely. Place devices on an isolated, segmented network behind a firewall to limit exposure of management interfaces. Use a VPN when accessing devices remotely to encrypt all traffic in transit. Monitor network traffic for unencrypted sensitive data leaving the management interface. Restrict network access to management interfaces using access control lists (ACLs) to only trusted hosts. Refer to and follow all steps in the product hardening guide or the JCI universal hardening guide found here: https://www.johnsoncontrols.com/trust-center/cybersecurity/resources . These mitigations reduce risk but may not fully remediate the vulnerability. Users should update to the fixed versions when operationally feasible. Mitigation Users should review logs, network telemetry, device events, and security monitoring tools for activity involving EasyIO NEO versions EC and CW. Relevant detection information may include: Unencrypted HTTP traffic to or from the device management interface on port 80. Network captures showing cleartext credentials or session tokens in HTTP requests. Unexpected devices or IP addresses accessing the web management console. ARP spoofing or other man-in-the-middle indicators on the local network segment. Unauthorized configuration changes that may indicate credential interception. Mitigation The recommendations provided within Johnson Controls Hardening Guide should always be applied to minimize security risk. Visit the Johnson Controls Trust Center Cybersecurity website to access the latest Hardening Guidelines and cybersecurity best practices - https://www.johnsoncontrols.com/trust-center/cybersecurity/resources. https://www.johnsoncontrols.com/trust-center/cybersecurity/resources Mitigation For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2026-30. https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories Relevant CWE: CWE-319 Cleartext Transmission of Sensitive Information Metrics CVSS Version Base Score Base Severity Vector String 3.1 5.4 MEDIUM CVSS:3.1/AV:N/AC:H/PR:L/UI:R/S:U/C:H/I:L/A:N 4.0 5.9 MEDIUM CVSS:4.0/AV:N/AC:H/AT:P/PR:L/UI:P/VC:H/VI:L/VA:L/SC:N/SI:N/SA:N Acknowledgments Gabriele Gardois reported this vulnerability to Johnson Controls Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity. Revision History Initial Release Date: 2026-10-01 Date Revision Summary 2026-10-01 1 Initial Republication of Johnson Controls Product Security Advisory JCI-PSA-2026-30 Legal Notice and Terms of Use
Impact
Johnson Controls EasyIO Neo Series EC Controllers V3.3b62, V3.3b63; EasyIO Neo Series CW Controllers V3.3b24, V3.3b25
Exploitation Status
No active exploitation has been reported at this time. However, organizations should still apply patches promptly as proof-of-concept code may exist.
Timeline
Disclosed on 2026-10-01
Remediation
Users should upgrade to EC firmware V3.3b64 and CW firmware V3.3b26. If immediate updates are not possible, users should enable HTTPS/TLS for all management access, disable HTTP access, segment devices behind a firewall, use a VPN for remote access, and monitor network traffic for unencrypted sensitive data.
Additional Information
This threat intelligence is aggregated from trusted cybersecurity sources. For the most up-to-date information, technical details, and official vendor guidance, please refer to the original article linked below.
Related Topics: This incident relates to CVE, Vulnerability, Patch, and 2 more.