Johnson Controls EasyIO Neo Series EC and CW Controllers
Overview
Johnson Controls has reported a vulnerability in its EasyIO Neo Series EC and CW Controllers that could allow attackers to access sensitive information. This issue affects multiple versions of the EC and CW Controllers, specifically versions V3.3b63, V3.3b62, V3.3b25, and V3.3b24. If exploited, this vulnerability could lead to further attacks on systems that utilize these devices, which are commonly used for building automation, including HVAC and lighting control. Users are urged to upgrade to the fixed firmware versions V3.3b64 for EC Controllers and V3.3b26 for CW Controllers as soon as possible. In the meantime, organizations should implement physical access controls and monitor network traffic to mitigate potential risks.
Key Takeaways
- Affected Systems: Johnson Controls EasyIO Neo Series EC Controllers V3.3b63, V3.3b62; Johnson Controls EasyIO Neo Series CW Controllers V3.3b25, V3.3b24
- Action Required: Users should upgrade to fixed versions: EC firmware V3.
- Timeline: Disclosed on 2026-10-01
Original Article Summary
View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to gain access to sensitive information that could be used to conduct further attacks against the system. The following versions of Johnson Controls EasyIO Neo Series EC and CW Controllers are affected: EasyIO Neo Series EC Controllers V3.3b63 (CVE-2026-64892) EasyIO Neo Series EC Controllers V3.3b62 (CVE-2026-64892) EasyIO Neo Series CW Controllers V3.3b25 (CVE-2026-64892) EasyIO Neo Series CW Controllers V3.3b24 (CVE-2026-64892) CVSS Vendor Equipment Vulnerabilities v3 3.5 Johnson Controls Johnson Controls EasyIO Neo Series EC and CW Controllers Exposure of Sensitive Information to an Unauthorized Actor Background Critical Infrastructure Sectors: Critical Manufacturing, Commercial Facilities, Government Services and Facilities, Transportation Systems, Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: Ireland Vulnerabilities Expand All + CVE-2026-64892 Johnson Controls is aware of a vulnerability in EasyIO Neo Series EC and CW Controllers relating to an attacker gaining access to sensitive information that could be used to conduct further attacks against the system. The EC and CW are programmable edge controllers designed for building automation and control systems, used to manage and automate various building functions including HVAC, lighting, and energy management, supporting open protocols such as BACnet and Modbus for adaptable system connections. View CVE Details Affected Products Johnson Controls EasyIO Neo Series EC and CW Controllers Vendor: Johnson Controls Product Version: Johnson Controls EasyIO Neo Series EC Controllers: V3.3b63, Johnson Controls EasyIO Neo Series EC Controllers: V3.3b62, Johnson Controls EasyIO Neo Series CW Controllers: V3.3b25, Johnson Controls EasyIO Neo Series CW Controllers: V3.3b24 Product Status: known_affected Remediations Mitigation Johnson Controls released fixed versions for EasyIO Neo Series EC and CW Controllers. Users should upgrade to the fixed version or later as soon as operationally feasible. The fix is available in EC firmware V3.3b64 and CW firmware V3.3b26. Contact your Johnson Controls representative or authorized EasyIO distributor. Mitigation Before applying updates in production ICS/OT environments, users should review operational impact, backup relevant configurations, test updates in a non-production environment where feasible, and follow applicable change-management and safety procedures. Mitigation If immediate update is not possible, Johnson Controls recommends the following mitigations: Implement physical access controls to prevent unauthorized personnel from reaching device debug ports. Monitor network traffic to and from affected devices for unusual or unauthorized access attempts. Apply the principle of least privilege to all accounts and services that interact with the affected devices. Where possible, apply firmware updates that disable debug interfaces or require authentication before granting debug access. Implement intrusion detection/prevention systems to monitor for exploitation attempts. Refer to and follow all steps in the product hardening guide or the JCI universal hardening guide found here: https://www.johnsoncontrols.com/trust-center/cybersecurity/resources . These mitigations reduce risk but may not fully remediate the vulnerability. Users should update to the fixed versions when operationally feasible. Mitigation For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2026-20. https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories Relevant CWE: CWE-200 Exposure of Sensitive Information to an Unauthorized Actor Metrics CVSS Version Base Score Base Severity Vector String 3.1 3.5 LOW CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:U/C:L/I:N/A:L 4.0 4.8 MEDIUM CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:P/VC:L/VI:N/VA:L/SC:N/SI:N/SA:N Acknowledgments Gabriele Gardois reported this vulnerability to Johnson Controls Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. The recommendations provided within Johnson Controls Hardening Guide should always be applied to minimize security risk. Visit the Johnson Controls Trust Center Cybersecurity website to access the latest Hardening Guidelines and cybersecurity best practices - https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories . CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-10-01 Date Revision Summary 2026-10-01 1 Initial Republication of Johnson Controls Product Security Advisory JCI-PSA-2026-20 Legal Notice and Terms of Use
Impact
Johnson Controls EasyIO Neo Series EC Controllers V3.3b63, V3.3b62; Johnson Controls EasyIO Neo Series CW Controllers V3.3b25, V3.3b24
Exploitation Status
No active exploitation has been reported at this time. However, organizations should still apply patches promptly as proof-of-concept code may exist.
Timeline
Disclosed on 2026-10-01
Remediation
Users should upgrade to fixed versions: EC firmware V3.3b64 and CW firmware V3.3b26. If immediate updates are not feasible, recommended mitigations include implementing physical access controls, monitoring network traffic for unauthorized access, applying the principle of least privilege for accounts interacting with the devices, and using intrusion detection systems.